Fraunhofer ISE

  das Haus

definitions and explanations

  Building


  heated area:   138 m²

  space heating demand:  ca. 145 kWh/m²a

  number in household:  5


  Heating system


  thermal power:  11 kW

  heat source:  outside air

  heat distribution:  underfloor heating


  Evaluation

  

Outside air is used as heat source for this system. The heating circuit contains a buffer storage, the DHW circuit contains a DHW storage. Underfloor heating and low inlet temperatures provide good preconditions for the heat pump system.   

Efficiency amounted to 2.9 in 2010 and thus reflects the average of air source heat pumps of 2.9. The fan's share of 8 % of the overall energy demand lies above the average of 7 % and therefore slightly influences the SPF negatively. As the back-up heater was not used, efficiency is influenced positively. The share of DHW of 11 % in 2010 lies below the average of 19 % and thus influences efficiency positively due to the low temperature level needed for heating.

anlagenschema Click on the picture to see current data

energy balances and seasonal performance factors SPF:

2008

2009

2010

2011

2012

2013

gelb compressor & controller grau fan schwarz back-up heater rot heating blau DHW gruen SPF strom average energie average AZ average
Click on the chart to see the average monthly data

Average daily temperatures:

anlagenschema anlagenschema anlagenschema outside air temperature        heating circuit                   DHW circuit