definitions and explanations

  Building


  heated area:                  320 m²

  space heating demand:  ca. 80 kWh/m²a

  number in household:     5


  Heating System


  thermal power:     12 kW

  heat source:        ground
                            ground water probe
                            (length: 300 m)

  heat distribution:  underfloor heating


  Evaluation

  

The heat source for this system is a borehole with a length of 300m. It is filled with water only. The heating circuit is operated without buffer storage. The DHW cicuit contains a DHW storage. Due to higher inlet temperatures in the brine circuit and underfloor heating which can be operated with low inlet temperatures, good preconditions for the heat pump are created.   

Efficiency values of 5.1 in 2010 are far above the average of 3.9 for ground source heat pumps. This results from low temperatures in the heating circuit and very high temperatures in the brine circuit in winter. The water pump's share of 3 % on the total electrical energy demand is below the average of 6 % which has a positive effect on the SPF. In 2010 the share of DHW of 5 % was below the average of 18 % and further increases efficiency.

anlagenschema Click on the picture to see current data

energy balances and seasonal performance factors SPF:

2009

2010

2011

2012

2013

2014

2015

gelb heat pump (compressor & controller) grau water pump schwarz back-up heater
rot heating blau DHW gruen SPF
strom average energie average AZ average
Click on the chart to see the average monthly data

Average daily temperatures:

anlagenschema anlagenschema anlagenschema water circuit                       heating circuit                   DHW circuit