heated area: 166 m² space heating demand: 78 kWh/m²a number in household: 2 Heating System thermal power (B0/W35): 9,2 kW* heat source: ground source 2 boreholes (total length 160 m) heat distribution: floor heating Evaluation The heat source system is equipped with 2 boreholes with a total length of 160 m. The heat pump contains an integrated DHW storage. A circulation pump is used for DHW supply, in addition a buffer storage is installed in the heating circuit. Furthermore a passive cooling module is installed in the system. Due to underfloor heating and low inlet temperatures, there are good preconditions for the heat pump system. Efficiency of 3.9 in 2010 reflected the average of this type of system.
Good efficiency values can be explained by low inlet temperatures in the heating circuit and high temperatures in the brine circuit in winter.
The brine pump's 12 % share of the total electrical energy demand is above the average of 6 % and thus influences the SPF negatively.
In 2010 the share of DHW amounted to 11 % and this lied below the average of 18 % and is responsible for good efficiency values as a low temperature level for the heating circuit was needed. |
Click on the picture to see current data
energy balances and seasonal performance factors SPF:
space heating DHW SPF Click on the chart to see averagy monthly data Average daily inlet temperatures:Brine circuit Heating circuit DHW circuit |